Q: Hoe kan ik ombouwen naar bereik van 10 A in plaats van 100A

尋ねた Janos に 2020-01-26 12:28:43

grfloater Instead of passing a single loop of the load line through the Current Transformer, wind 10 turns of a suitable insulated cable. 10A can be on 1.5 mm2 cable, so it could fit the CT opening, for 10 turns. Then, you should divide what you are reading by 10, i.e. if you read 5.4A, it would be 0.54A